Product details
CCX-8/K Reinforced Air Insulated Busway System is an improved product based on air-type busway. The conductor of the buswayr is made of electrolytic copper containing more than 99,95% copper. After processing, it is wrapped with insulating film at first and then covered with PVC pipe heat shrink treatment.
The copper bar is protected by double insulation and the insulation performance is greatly improved, The phase and the ground are separated by an insulating block. And then sealing in a grounded metal housing.
The side plate of the housing is made of high-quality cold-rolled steel plate with high strength, After processing and forming, it is electrostatic sprayed with good anti-corrosion performance. The cover plate and the side plate of housing are made of aluminum-magnesium alloy material with beautiful appearance.
Product parameter
Specifications | IEC60439-1:1999、GB7251.1-2005 IEC60439-2:2000、GB7251.2-2006、JB/T8511-1996 |
(KA)Rated peakcurrent | 25 | 30 | 40 | 50 | 65 | 75 | 90 | ||||||||||||||||||||||||
Ambient temperature | -15/+40 | (KA)Rated short-timewithsatand current | 50 | 63 | 84 | 105 | 143 | 165 | 198 | ||||||||||||||||||||||||
Height above sea level | Not exceeding 2000m | Temperature rise test(℃) | ≤45 | ≤48 | ≤43 | ≤50 | ≤53 | ||||||||||||||||||||||||||
Degree of protection | Ip30(Feed ventilation type)Ip40/Ip54(Plug protection type) | Insulation(MΩ) | ≥200 | ||||||||||||||||||||||||||||||
Unit Length | ≤9 | Cleaeance(mm) | ≥10 | ||||||||||||||||||||||||||||||
UiRated insulation Voltage | 690/1000 | Clearance(mm) | ≥12.5 | ||||||||||||||||||||||||||||||
UeRated aperationaIVoltage | 380/660 | PE(Ω)Creepage distance | <0.01 | ||||||||||||||||||||||||||||||
Frequence(HZ) | 50(60) | Power withstand voltage | 50Hz、10KV、1min No breakdown,No flashover | ||||||||||||||||||||||||||||||
Rated current(A) | 160 | 200 | 250 | 315 | 400 | 500 | 630 | 800 | 1000 | 1250 | 1600 | 2000 | 2500 | 3150 | 4000 | 5000 | Mounting | Vertical or horizontal | |||||||||||||||
Resistance R20(uΩ/m) | 114. | 94.4 | 94.4 | 82.5 | 73 | 71.9 | 66.5 | 61.4 | 46.2 | 35.2 | 26.9 | 21.4 | 17.2 | 14.3 | 10.5 | 6.8 | Tap-off unit amount | minimum 0.5m/unit(plug in two sides available) | |||||||||||||||
Resistance X20(uΩ/m) | 52 | 47.2 | 47.2 | 45.5 | 43.6 | 40.9 | 38.2 | 33.2 | 26.4 | 20.2 | 15.5 | 11.9 | 9.7 | 8.2 | 7.8 | 6 | Fixing intervals(m) | 2.5 | 2 | 1.5 | |||||||||||||
Total Impedance Z20(uΩ/m) | 125.4 | 106 | 106 | 94.9 | 85 | 82.7 | 76.7 | 69.8 | 53.8 | 40.6 | 31 | 24.1 | 19.6 | 16.5 | 13.5 | 9.07 | For balanced load(kg/m) | 15 | 20 | 30 | 55 | 85 | 150 | ||||||||||
Voltage drop (V/m)(COSφ=0.9h) | 0.02 | 0.026 | 0.026 | 0.028 | 0.034 | 0.041 | 0.048 | 0.056 | 0.054 | 0.051 | 0.049 | 0.048 | 0.049 | 0.052 | 0.054 | 0.045 | For concentrated load(kg) | 13 | 17 | 26 | 50 | 76 | 100 |