19+ years experience in power transmission & distribution equipment manufacturing, one-stop solution provider for electrical equipment.
Product details
This busway is a new product which developed after summarizing many years of experience in busway production, It is an essential transmission and distribution equipment for firefighting system.
Product parameter
Specifications | IEC60439-1:1999、GB7251.1-2005 IEC60439-2:2000⊥GB7251.2-2006⊥JB/T8511-1996 |
(KA)Rated short-timewithsatand current | 20 | 30 | 65 | ||||||||
Ambient temperature | -15/+40 | (KA)Rated peakcurrent | 42 | 63 | 176 | ||||||||
Height above sea level | not exceeding 2000m | Temperature rise test(℃) | ≤45 ≤50 | ||||||||||
Degree of protection | Ip66 | Insulation(MΩ) | ≥200 | ||||||||||
Unit Length | ≤6 | Cleaeance(mm) | ≥10 | ||||||||||
UiRated insulation Voltage | 690/1000 | Clearance(mm) | ≥12.5 | ||||||||||
UeRated aperationalVoltage | 380/660 | PE Creepage distance | <0.01 | ||||||||||
Frequen ce(HZ) | 50(60) | Power withstand voltage | 50Hz、10KV/1min No breakdown,No flashover | ||||||||||
Rated current(A) | 50 | 630 | 800 | 1000 | 1250 | 1600 | Mounting | Vertical or horizontal | |||||
Resistance R20(uΩ/m) | 71.9 | 66.5 | 61.4 | 46.2 | 35.2 | 26.9 | Tap-off unit amount | minimum 0.6/unit | |||||
Resistance X20(uΩ/m) | 40.9 | 38.2 | 33.2 | 26.4 | 20.2 | 15.5 | Fixing intervals(m) | 2.5 | 2 | 1.5 | |||
Total Impedance Z20(uΩ/m) | 82.7 | 76.7 | 69.8 | 53.8 | 40.6 | 31 | For balanced load(kg/m) | 72 | 110 | 195 | |||
Voltage drop (V/m) (COSφ=0.9h) | 0.041 | 0.048 | 0.056 | 0.054 | 0.051 | 0.049 | For concentrated load(kg) | 65 | 99 | 130 |